The fire safety roller shutter requirements in Singapore cover more than simply choosing a shutter with a fire-resistant curtain. Depending on where the shutter is installed, requirements can involve fire resistance, activation methods, closing behaviour, emergency operation, product certification and integration with the building’s fire safety systems.
Fire shutters are commonly used as part of a building’s compartmentation strategy, helping limit the spread of fire and smoke between designated areas. However, they should not be treated as interchangeable with ordinary security shutters, and the applicable requirements depend on the building design and intended location.
Why Are Fire Safety Roller Shutters Important in Singapore?

Fire roller shutters form part of a wider passive fire protection strategy by helping protect openings where fire compartments need to be maintained. SCDF’s Fire Code permits fire shutters to be used as compartment walls in specified situations, but excludes certain locations such as fire command centres and means of escape.
The need for effective fire protection remains significant. SCDF recorded 2,050 fires in Singapore in 2025, a 3% increase from 2024, while fires at non-residential premises increased by 13.5%. This figure covers all fires rather than incidents involving fire shutters specifically, but it illustrates why fire protection remains an important consideration for commercial and industrial properties.
For buildings such as warehouses, factories, shopping malls, hospitals and logistics facilities, a properly specified fire shutter can form one part of the overall strategy for containing fire and protecting occupants and assets.
What Are the Main Fire Safety Roller Shutter Requirements?
The exact requirements vary according to the shutter’s location and purpose, but several key areas should be considered.
For projects that require a fire-resistant shutter, businesses can explore the available fire-rated roller shutter options to better understand the protection ratings, configurations and applications available for different building requirements.
1. The Shutter Must Have the Required Fire Resistance
A fire shutter used to protect an opening in a compartment wall or floor needs to provide the necessary fire resistance, including thermal insulation where required, that is appropriate to the compartment construction. SCDF’s Fire Code specifically addresses this under Clause 3.7.7.
The required rating should therefore be determined from the building’s approved fire safety design rather than selected simply because a product is advertised as “fire-rated.”
Standard Rolling Shutters currently lists fire-rated roller shutters with configurations including insulated and non-insulated options, with the appropriate specification depending on the project.
2. The Shutter Must Meet the Applicable Product Standard
SCDF’s Table 11A identifies fire shutters/fire curtains as regulated fire safety products. The table lists SS 489 Clause 5 or EN 1634-1 as acceptable standards, with certification under the Product Listing Scheme.
This is an important distinction for building owners and project teams. A supplier’s statement that a shutter is “fire-resistant” is not, by itself, the same as demonstrating that the product meets the applicable regulatory and certification requirements.
SCDF explains that regulated fire safety products under its Product Listing Scheme must be certified by recognised certification bodies, and Qualified Persons are responsible for checking that applicable products have valid Certificates of Conformity and that the certification matches the products actually used.
How Should a Fire Shutter Operate During an Emergency?
Fire shutters need an appropriate activation and closing arrangement based on where they are installed.
Under SCDF Fire Code Clause 3.7.7, commonly used vertical, horizontal and lateral fire shutters are required to comply with SS 489 and the additional Fire Code provisions. For certain vertical shutters, activation releases the curtain so that it descends under gravity at a controlled rate. Electrically operated shutters can be driven by a motor following fire alarm activation and require appropriate emergency power and fire-rated power and signal cables.
For vertical fire shutters:
- A shutter up to 6 metres high must have a maximum full-closure time of 30 seconds under the specified Fire Code provision.
- A shutter more than 6 metres and up to 12 metres high must have a maximum full-closure time of 60 seconds.
- The specified descending speed must not exceed 0.2 metres per second.
These figures apply to the specific Fire Code provisions for fire shutters used in compartmentation. They should not be interpreted as a universal specification for every type or location of shutter.
What About Fire Shutters Located Across Escape Routes?
This is one area where businesses need to be particularly careful because fire compartmentation and means of escape are not the same thing.
SCDF states that fire shutters used as compartment walls do not apply to certain means-of-escape locations. Separately, Clause 2.3.9h provides requirements for sliding doors and roller shutters installed across exit access routes.
For manually operated roller shutters permitted across applicable exit access routes:
- They must be capable of being opened and closed manually from either side.
- The maximum opening force is 30 N.
- Where occupant load exceeds 50 persons, additional conditions apply, including keeping the shutter fully open while the premises is occupied unless an applicable alternative such as a wicket door is provided.
- A wicket door incorporated into a shutter must meet specified exit-access-door requirements.
For powered sliding doors or roller shutters, SCDF specifies additional requirements, including fail-safe operation and a manual override mechanism in applicable situations. Some tenant-owned or tenant-operated systems have specific exceptions from direct fire-alarm linking when the stated conditions are met.
This is why the position of the shutter within the building should be established before selecting the product.
Fire Shutter Requirements: Compartmentation vs Escape Routes
| Requirement area | Fire shutter used for compartmentation | Shutter across applicable escape access |
|---|---|---|
| Main purpose | Limit fire spread between compartments | Maintain safe access/egress |
| Fire resistance | Required according to application | Depends on the specific door/shutter arrangement |
| Fire alarm activation | Applicable according to location/design | Powered systems have specific requirements |
| Emergency operation | Controlled closure | Must not prevent required escape |
| Manual operation | Depends on system | Specific manual opening requirements apply |
| Product certification | Regulated products may require CoC | Depends on product/application |
| Design approval | Project-specific | Project-specific |
The table is a practical summary rather than a substitute for the Fire Code. A Qualified Person should determine the applicable provisions for an actual building project.
Does a Fire Shutter Need Certification in Singapore?
For regulated fire safety products, certification is an important part of the compliance process. SCDF states that regulated fire safety products are certified by Certification Bodies accredited by the Singapore Accreditation Council, and products that meet the applicable requirements receive a Certificate of Conformity (CoC).
Qualified Persons must verify, where applicable:
- The product is a compliant regulated fire safety product.
- The Certificate of Conformity is valid.
- The product installed matches the CoC.
- Required serial labels or Declarations of Compliance are present and accurate.
This documentation is particularly important for projects involving new construction, additions and alterations or upgrades to existing fire safety systems.
How Should Businesses Select a Compliant Fire Shutter?
Choosing a fire shutter should begin with the building’s approved fire safety requirements rather than with a catalogue specification.
A practical process is:
- Identify the shutter’s location.
Determine whether it protects a compartment opening, special room, atrium, lift lobby or another area.
- Confirm the required fire resistance.
Establish the required rating from the project’s fire safety design.
- Check whether the product is regulated.
Verify the applicable certification and Product Listing Scheme requirements.
- Review the activation method.
Determine whether the system uses gravity operation, fire alarm activation, smoke detection or another permitted arrangement.
- Check the opening dimensions.
Width, height, headroom and structural conditions can affect the appropriate system.
- Confirm emergency operation.
Make sure manual override, emergency power and other required safety features are incorporated where applicable.
- Test and document the completed installation.
The system should be checked as part of the project’s fire safety and commissioning process.
In our experience, the most useful discussions happen before installation begins. Confirming the shutter’s location, fire compartmentation role and operational requirements early can prevent costly changes later.
A Practical Example: Warehouse Fire Compartmentation
Consider a warehouse divided into different fire compartments. A large opening between two sections needs a fire shutter so that the opening can be protected when the system is activated.
The project team would first establish the required fire resistance and confirm that a fire shutter is permitted for that application. They would then verify the product’s certification, activation method, dimensions and closing characteristics before installation and testing.
The important point is that the shutter is designed as part of the warehouse’s overall fire protection system—not simply installed as a stronger version of an ordinary roller shutter.
For specialised healthcare environments, the requirements can become even more specific because hospitals contain vulnerable occupants, critical equipment and areas that may have different operational risks. Businesses and healthcare operators can refer to fire shutters for hospitals in Singapore for more information about hospital-specific fire shutter applications.
Why Is Professional Installation Important?
Fire shutters are safety-critical systems, so correct installation is part of their overall performance. Even a certified product can be affected by incorrect dimensions, poor alignment, unsuitable structural fixing, improper electrical connections or incomplete integration with the building’s fire safety systems.
Professional installation should address:
- Site assessment and measurements
- Structural support and mounting
- Guide alignment
- Curtain and barrel installation
- Motor and control systems
- Fire alarm or detector integration
- Emergency power where required
- Manual override arrangements
- Functional and operational testing
- Relevant certification and documentation
Standard Rolling Shutters provides fire-rated roller shutter installation, repair, replacement and maintenance services for commercial and industrial buildings in Singapore. Its fire-rated shutter range includes systems designed for applications such as industrial buildings, shopping centres and warehouses.
What Maintenance Does a Fire Roller Shutter Need?
Compliance does not end when installation is complete. Regular inspection and maintenance help ensure that the shutter remains operational and that important components do not deteriorate unnoticed.
Maintenance should consider:
- Curtain and guide condition
- Motor and control operation
- Fire alarm connection
- Automatic activation
- Closing movement
- Emergency release or manual override
- Electrical connections
- Physical obstructions around the shutter
Standard Rolling Shutters also provides fire roller shutter maintenance services covering inspection, testing, servicing and repair.
A maintenance programme should be matched to the building, shutter type, usage and applicable fire safety requirements rather than relying on a generic interval.
Conclusion: Meeting Fire Safety Roller Shutter Requirements in Singapore

Understanding the fire safety roller shutter requirements in Singapore is essential when planning a new installation or upgrading an existing building. The correct solution depends on the shutter’s location, fire compartmentation role, required fire resistance, activation method, certification and relationship with the building’s means of escape.
For regulated fire safety products, compliance also involves more than purchasing a product described as fire-rated. SCDF’s requirements cover certification, product verification and responsibilities for Qualified Persons, while the Fire Code sets specific requirements for fire shutter operation and applications.
Standard Rolling Shutters provides fire-rated roller shutter solutions together with installation, repair, replacement and maintenance support for commercial and industrial properties in Singapore. For a project-specific assessment of your opening, fire protection requirements and operating conditions, visit Standard Rolling Shutters to discuss the appropriate shutter solution.
If you are unsure which fire-rated roller shutter configuration is suitable for your building, a professional assessment can help clarify the required fire rating, dimensions, operating method and installation considerations. You can contact Standard Rolling Shutters to discuss your project requirements and the appropriate shutter solution.
Frequently Asked Questions
What are the fire safety roller shutter requirements in Singapore?
The requirements depend on the shutter’s location and purpose. Relevant provisions can cover fire resistance, applicable product standards, certification, activation, closing behaviour, emergency operation and integration with fire safety systems. SCDF Fire Code Clauses 2.3 and 3.7 are particularly relevant to roller shutters used in escape access and fire compartmentation.
Does every roller shutter need to be fire-rated in Singapore?
No. A standard security roller shutter and a fire-rated shutter serve different purposes. Whether a fire-rated shutter is required depends on the building’s approved fire safety design, the location of the opening and its role in fire compartmentation or other fire safety provisions.
What standard applies to fire shutters in Singapore?
SCDF’s current Table 11A identifies SS 489 Clause 5 or EN 1634-1 as acceptable standards for fire shutters/fire curtains under the Product Listing Scheme, subject to the applicable requirements.
Do fire shutters need to connect to a fire alarm?
The activation arrangement depends on where and how the fire shutter is used. SCDF Fire Code specifies different activation methods for different applications, including fire alarm systems, local smoke detectors and fusible links in specified circumstances.
Can a fire shutter be installed across an escape route?
Certain sliding doors and roller shutters are permitted across applicable exit access routes, but specific conditions apply. These can include manual opening force limits, requirements for keeping shutters open during occupancy, wicket doors and fail-safe/manual override arrangements for powered systems.